14.26
SEL-311C Relay
Instruction Manual
Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221F to SEL-311C Settings Conversion Guide
Application Settings
From Access Level 2, set the SEL-311C application setting to “221F” as
shown below:
=>>
SET APP TERSE <Enter>
Line Parameter Settings:
Application
(311C,221G,221G5,221H,221F,221F3,221C,221-16,2PG10)APP = 311C ?
221F <Enter>
Enable Settings:
Fault Location(Y,N) EFLOC = Y ?
END <Enter>
Save Changes(Y/N)?
Y <Enter>
Settings saved
=>>
Convert SEL-221F
Primary Quantities to
SEL-311C Secondary
Quantities
All SEL-221F current settings must be converted from primary to secondary
amps to be used in the SEL-311C. Divide the SEL-221F current setting by the
current transformer ratio setting (CTR) to make the change.
SEL-221F impedance settings must be converted from percent of primary line
impedance to secondary impedance in ohms. For example, the Zone 1 distance
setting in the SEL-311C (Z1P) is calculated as
Equation 14.4
Convert SEL-221F
Settings to SEL-311C
Settings
shows all the SEL-311C settings that must be entered for the relay
to perform protection similar to the SEL-221F when APP = 221F. Calculate
each SEL-311C setting from the corresponding SEL-221F setting using the
formula shown. Instruction manual references are to subsection headings
rather than to section headings.
Carefully note the difference between the SEL-311C and SEL-221F in the
implementation of certain protection and logic schemes. For example,
reclosing and synchronism check settings do not correspond exactly between
the two relays. Always thoroughly test logic schemes to be sure they operate
as intended.
where:
Z1% = the SEL-221F distance reach setting
Z1MAG = the SEL-311C positive-sequence line impedance setting
in secondary ohms.
Z1P = the SEL-311C Zone 1 reach setting in secondary ohms.
Z1P
Z1%
100
------------
Z1MAG
•
=
Table 14.13
SEL-311C Settings Calculated From SEL-221F Settings
(Sheet 1 of 3)
SEL-311C
Setting
a
Calculated From SEL-221F Settings
SEL-311C Instruction
Manual Section
SEL-221F Instruction
Manual Section
RID
None
Settings Sheets for the
SEL-311C Relay
Section 3—Set
TID
= ID
CTR
= CTR
Settings Sheets for the
SEL-311C Relay
Section 5—Current and Potential
Transformer Ratio Selection
CTRP
= CTR
PTR
= PTR
PTRS
= SPTR
Z1MAG
Settings Sheets for the
SEL-311C Relay
Section 5—R1, X1, R0, X0, and
Line Length (LL)
R1
2
X1
2
+
(
)
=
CTR
PTR
------------
•
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...