H.2
SEL-311C Relay
Instruction Manual
Date Code 20060320
Setting SEL
OGIC
Control Equations
Relay Word Bits
Relay Word Bits
Most of the protection and control element
logic outputs
shown in the various
Section 3: Distance, Out-of-Step, Overcurrent, Voltage,
Synchronism Check, and Frequency Elements
through
Monitor and Metering Functions
are Relay Word bits (labeled as such in the
figures). Each Relay Word bit has a label name and can be in either of the
following states:
➤
1 (logical 1) or
➤
0 (logical 0)
Logical 1 represents an element being picked up, timed out, or otherwise
asserted.
Logical 0 represents an element being dropped out or otherwise deasserted.
Complete listings of Relay Word bits and their descriptions are referenced in
and
Relay Word Bit
Operation Example–
Phase Time-
Overcurrent Element
51PT
As an example of protection element operation via the logic output of Relay
Word bits, a phase time-overcurrent element is examined. Refer to phase time-
overcurrent element 51PT in
. Read the text that accompanies
and following text). The following Relay Word bits
are the logic outputs of the phase time-overcurrent element:
51P indication that the maximum phase current magnitude is above the
level of the phase time-overcurrent pickup setting 51PP
51PT indication that the phase time-overcurrent element has timed out on
its curve
51PR indication that the phase time-overcurrent element is fully reset
Phase Time-Overcurrent Element 51PT Pickup Indication
If the maximum phase current is
at or below
the level of the phase time-
overcurrent pickup setting 51PP, Relay Word bit 51P is in the following state:
51P = 0 (logical 0)
If the maximum phase current is
above
the level of the phase time-overcurrent
pickup setting 51PP, Relay Word bit 51P is in the following state:
51P = 1 (logical 1)
If the maximum phase current is
above
the level of the phase time-overcurrent
pickup setting 51PP, phase time-overcurrent element 51PT is either timing on
its curve or is already timed out.
Phase Time-Overcurrent Element 51PT Time-Out Indication
If phase time-overcurrent element 51PT is
not timed out
on its curve, Relay
Word bit 51PT is in the following state:
51PT = 0 (logical 0)
If phase time-overcurrent element 51PT is
timed out
on its curve, Relay Word
bit 51PT is in the following state:
51PT = 1 (logical 1)
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...