5.33
Date Code 20060320
Instruction Manual
SEL-311C Relay
Trip and Target Logic
Front-Panel Target LEDs
51 Target LED
The
51
target LED illuminates at the rising edge of trip if a time-overcurrent
element (51PT, 51GT, or 51QT) is in the SEL
OGIC
equation that caused the
trip.
FAULT TYPE Target LEDs
A, B, and C Target LEDs
A
(Phase A) target LED is illuminated at the rising edge of trip if a protection
element causes the trip and Phase A is involved in the fault (likewise for
B
[Phase B] and
C
[Phase C] target LEDs).
G Target LED
G
target LED is illuminated at the rising edge of trip if a ground distance or
residual ground overcurrent element causes the trip or was picked up and
timing to trip.
Zone LEDs
Zone/Level LEDs illuminate at the rising edge of trip for the lowest zone
number in the SEL
OGIC
control equation that caused the trip (M1P, M2P, M3P,
M4P, Z1G, Z2G, Z3G, Z4G, 50P1, 67P1, 67P2, 67P3, 67G1, 67G2, 67G3,
67G4, 67Q1, 67Q2, 67Q3, 67Q4, Z2PG2S, 67QG2S).
These elements need only be present in the SEL
OGIC
control equation
that causes the trip in order to participate in the illuminating of front-
panel targets. No consideration is made as to how the element is used. For
example, assume the SEL
OGIC
control equation TR = IN101 * Z1G +
Z2G. In this case, if the Z1G element is set at the rising edge of TRIP, the
ZONE1
target will light even though IN101 is not set and the cause of the
trip was Z2G.
{TARGET RESET/LAMP
TEST} Front-Panel
Pushbutton
When the
{TARGET RESET/LAMP TEST}
front-panel pushbutton is pressed:
➤
All front-panel LEDs illuminate for one (1) second.
➤
All latched target LEDs (target LEDs numbered 2–6 and 9–15
in
) are extinguished (unlatched).
Other Applications for the Target Reset Function
. The combination of the
{TARGET RESET}
pushbutton and the
TAR R
(Target Reset) serial port command is available as
Relay Word bit TRGTR. Relay Word bit TRGTR pulses to logical 1 for one
processing interval when either the
{TARGET RESET}
pushbutton is pushed or the
TAR R
(Target Reset) serial port command is executed.
Relay Word bit TRGTR can be used to unlatch logic. For example, refer to the
breaker failure logic in
. If a breaker failure trip occurs (SV7T
asserts), the occurrence can be displayed on the front panel with seal-in logic
and a rotating default display (see
Rotating Default Display (Only on Models
and
Rotating Default Display on page 11.12
):
SV8 =
(SV8 + SV7T) * !TRGTR
DP3 =
SV8
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...