12.12
SEL-311C Relay
Instruction Manual
Date Code 20060320
Standard Event Reports and SER
Standard 15/30/60/180-Cycle Event Reports
67P 1 2
67P1, 67P2
1
2
b
67P1 asserted
67P2 asserted
both 67P1 and 67P2 asserted
67P 3
67P3
3
67P3 asserted
67G 1 2
67G1, 67G2
1
2
b
67G1 asserted
67G2 asserted
both 67G1 and 67G2 asserted
67G 3 4
67G3, 67G4
3
4
b
67G3 asserted
67G4 asserted
both 67G3 and 67G4 asserted
67Q 1 2
67Q1, 67Q2
1
2
b
67Q1 asserted
67Q2 asserted
both 67Q1 and 67Q2 asserted
67Q 3 4
67Q3, 67Q4
3
4
b
67Q3 asserted
67Q4 asserted
both 67Q3 and 67Q4 asserted
DM P Q
PDEM, QDEM
P
Phase demand ammeter element PDEM picked up.
Q
Negative-sequence demand ammeter element QDEM picked up.
b
Both PDEM and QDEM picked up.
DM G
GDEM
*
Residual ground demand ammeter element GDEM picked up.
27 P
27A, 27B, 27C
A
A-phase instantaneous undervoltage element 27A picked up.
B
B-phase instantaneous undervoltage element 27B picked up.
C
C-phase instantaneous undervoltage element 27C picked up.
a
27A and 27B elements picked up.
b
27B and 27C elements picked up.
c
27C and 27A elements picked up.
3
27A, 27B, and 27C elements picked up.
27 PP
27AB, 27BC, 27CA
A
AB phase-to-phase instantaneous
undervoltage element 27AB picked up.
B
BC phase-to-phase instantaneous
undervoltage element 27BC picked up.
C
CA phase-to-phase instantaneous
undervoltage element 27CA picked up.
a
27AB and 27CA elements picked up.
b
27AB and 27BC elements picked up.
c
27BC and 27CA elements picked up.
3
27AB, 27BC and 27CA elements picked up.
27 S
27S
*
Channel VS instantaneous undervoltage element 27S picked up.
59 P
59A, 59B, 59C
A
A-phase instantaneous overvoltage element 59A picked up.
B
B-phase instantaneous overvoltage element 59B picked up.
C
C-phase instantaneous overvoltage element 59C picked up.
a
59A and 59B elements picked up.
b
59B and 59C elements picked up.
Table 12.4
Output, Input, Protection, and Control Element Event Report Columns
(Sheet 3 of 6)
Column Heading
Corresponding
Elements (Relay
Word Bits)
Symbol
Definition
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...