SEL-311C Relay
Instruction Manual
Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221-16 to SEL-311C Settings Conversion Guide
Convert SEL-221-16
Output Mask Logic
Settings to SEL
OGIC
Control Equations
See
Programmable Output Contact Mask Settings
in
Section 5: Applications
in the SEL
-221-16 Instruction Manual
for a description of output masks. In
the SEL-311C, output masks are replaced by SEL
OGIC
control equations as
.
shows all SEL-221-16 Relay Word bits, and an approximate
equivalent SEL-311C SEL
OGIC
expression, when setting APP = 221-16 in the
SEL-311C.
shows each SEL-221-16 Mask Logic Setting and the
equivalent SEL-311C SEL
OGIC
control equation. To convert an SEL-221-16
Mask Logic Setting to a SEL
OGIC
control equation, logically OR each
51GTC
(= 1
(= 32GF
= 51NTC (51GTC is an SEL-311C
SEL
OGIC
setting.)
= N)
= Y)
79OI1
= 79OI1
Section 6: Close and Reclose
Logic
Section 5—Reclose Logic
79RSD
= 79RS
79RSLD
= 79RS
52AEND
= 52BT (Pickup)
Switch-Onto-Fault Trip Logic
on page 5.7
Section 5—52BT Setting (52BT)
and Switch-Onto-Fault Protection
SOTFD
= 52BT (Dropout)
TDURD
= TDUR
Section 5—Trip Duration Timer
(TDUR)
SV1PU
= A1TP
Section 2—Miscellaneous Timers
SV1DO
= A1TD
a
SEL-311C phase-to-phase fault detector settings (50PP1, 50PP2, and 50PP3) are set to their minimum values and hidden. This
corresponds to SEL-221-16 setting 50P.
SEL-311C phase-to-ground and residual fault detector settings (50L1, 50L2, 50L3, 50GZ1, 50GZ2, and 50GZ3) are set to their minimum
values and hidden. This corresponds to SEL-221-16 setting 50NG.
SEL-221-16 function “Remote End Just Opened” (REJO) is not implemented in the SEL-311C.
b
Curve U1 in the SEL-311C is slightly different from curve 1 in the SEL-221-16. Time dial adjustments may be necessary.
Table 14.28
SEL-311C Settings Calculated From SEL-221-16 Settings
(Sheet 3 of 3)
SEL-311C
Setting
a
Calculated From SEL-221-16 Settings
SEL-311C Instruction
Manual Section
SEL-221-16 Instruction
Manual Section
Table 14.29
SEL-311C SEL
OGIC
Control Equation Equivalent to Each
SEL-221-16 Mask Logic Setting
SEL-221-16 Settings Mask
SEL-311C SEL
OGIC
Control Equations
MTU
TR
MPT
None
MTB
None
MTO
TRSOTF
MA1
OUT104
MA2
OUT105
MA3
OUT106
MA4
OUT107
MRI
79RI
MRC
79DTL
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...