7.32
SEL-311C Relay
Instruction Manual
Date Code 20060320
Inputs, Outputs, Timers, and Other Control Logic
Output Contacts
Output Contacts
and
show the example operation of output contact
Relay Word bits due to:
➤
SEL
OGIC
control equation operation
or
➤
PULSE
command execution
The output contact Relay Word bits in turn control the output contacts.
Alarm logic/circuitry controls the
ALARM
output contact (see
).
is used for the following discussion/examples. The output
operate similarly.
Factory Settings
Example
In the factory SEL
OGIC
control equation settings, four output contacts are
used:
OUT101 =
TRIP
(overcurrent tripping/manual tripping; see
OUT102 =
TRIP
OUT103 =
CLOSE
(automatic reclosing/manual closing; see
OUT104 =
KEY
(POTT key permissive trip; see
)
·
·
·
OUT107 =
0
(output contact
OUT107
not used—set equal to zero)
Operation of Output
Contacts for Different
Output Contact Types
Output Contacts OUT101 Through OUT107
.
The execution of the serial port command
PULSE
n
(
n
= OUT101 through
OUT107) asserts the corresponding Relay Word bit (OUT101 through
OUT107) to logical 1. The assertion of SEL
OGIC
control equation setting
OUT
m
(
m
= 101 through 107) to logical 1 also asserts the corresponding
Relay Word bit OUT
m
(
m
= 101 through 107) to logical 1.
The assertion of Relay Word bit OUT
m
(
m
= 101 through 107) to logical 1
causes the energization of the corresponding output contact OUT
m
coil.
Depending on the contact type (a or b), the output contact closes or opens as
demonstrated in
. An a type output contact is open when the output
contact coil is de-energized and closed when the output contact coil is
energized. A b type output contact is closed when the output contact coil is de-
energized and open when the output contact coil is energized.
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...