10.32
SEL-311C Relay
Instruction Manual
Date Code 20060320
Serial Port Communications and Commands
Command Explanations
The
TAR
command does not remap the front-panel target LEDs, as is done in
some previous SEL relays. But execution of the equivalent
TAR
command via
the front-panel display does remap the bottom row of the front-panel target
LEDs (see
, pushbutton
{OTHER}
).
Command
TAR SH1 10
is executed in the following example:
=>
TAR SH1 10 <Enter>
79RS 79CY 79LO SH0 SH1 SH2 SH3 SH4
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
79RS 79CY 79LO SH0 SH1 SH2 SH3 SH4
0 0 1 0 0 1 0 0
0 0 1 0 0 1 0 0
=>
Note that Relay Word row containing the SH1 bit is repeated 10 times. In this
example, the reclosing relay is in the Lockout State (79LO = logical 1), and
the shot is at shot = 2 (SH2 = logical 1). Command
TAR 31
will report the
same data since the SH1 bit is in Row 31 of the Relay Word.
TIM Command (View/Change Time)
TIM
displays the relay clock. To set the clock, type
TIM
and the desired
setting, then press
<Enter>
. Separate the hours, minutes, and seconds with
colons, semicolons, spaces, commas, or slashes. To set the clock to 11:30 PM
enter:
=>
TIM 23:30:00 <Enter>
23:30:00
=>
Table 10.9
TAR Command Options
TAR
n k
Shows Relay Word row number
n
(0–51).
k
is an optional parameter to
specify the number of times (1–32767) to repeat the Relay Word row
display. If
k
is not specified, the Relay Word row is displayed once.
TAR
name k
Shows Relay Word row containing Relay Word bit name (e.g.,
TAR 50P1
displays Relay Word Row 3). Valid names are shown in
and
.
k
is an optional parameter to specify the number
of times (1–32767) to repeat the Relay Word row display. If
k
is not
specified, the Relay Word row is displayed once.
TAR R
Clears front-panel tripping target LEDs:
TRIP
,
TIME
,
COMM
,
SOTF
,
51
,
A
,
B
,
C
,
G
,
Zone1
,
Zone2
,
Zone3
, and
Zone4
. Unlatches the trip logic for testing pur-
poses (see
). Shows Relay Word Row 0.
Table 10.10
SEL-311C Relay Word and Its Correspondence to TAR Command
TAR 0
(Front-Panel LEDs)
EN
TRIP
TIME
COMM
SOTF
RS
LO
51
TAR
1 (Front-Panel LEDs)
A
B
C
G
ZONE1
ZONE2
ZONE3
ZONE4
NOTE:
After setting date or time,
allow at least 60 seconds before
powering down the relay or the new
setting may be lost.
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...