Technical Data
92
Operating Manual ProNumeric XCI 600 Version 07/16
14
Technical Data
Electrical data
Supply voltage
DC 24V +-10%
Internal power consumption
max. 4 A (24 V)
Isolation
(from internal
electronics)
Ethernet / EtherCAT®
Yes (except LAN screen)
USB
No
DVI
No
RS232
No
Interfaces
RS 232
no stationary connection of serial units
galvanically isolated RS485 module (optional)
4x Ethernet (10/100/1000 MBit)
Programming, diagnostic and control unit interface, drive interface
(EtherCAT®)
7x USB 2.0
USB interface (e.g. mouse, keyboard, USB memory stick, etc.)
DVI
Monitor interface DVI-I (digital / analog)
Other technical data
Processor
Performance version 1
COMe-bIP2 i3-3217UE
(2x1.60GHz, 17W)
Memory
SDRAM
4 GB (max. 8 GB)
NVRAM
128 KB
SSD
>=32 GB
Additional information
PLC processing times
every 1000 instructions
Bit
0.018 ms
Byte / Word / DWord
0.005 ms
Integer (Add / Mul)
0.006 ms
Real (Add)
0.029 ms
Real-time memory
(adjustable)
Operating system
(data / program)
32768 kB
PLC memory
Programs
4096 kB
Flag retentive
256 kB
Flag not retentive
2048 kB
Dimensions / weight
Measurements
200 mm x 200 mm x 100 mm
Weight