First Steps with MULTIPROG
32
Operating Manual ProNumeric XCI 600 Version 07/16
5.2
Compiling a project and sending it to the XCI 600
To compile the project, select, <
Code> <Make>
(see: Figure 24)
(alternatively <F9> or the <
Make>
button).
Figure 24:
Compile Project
The message window below displays the progress of the compiler. Error
messages, warnings and other information are displayed here. Click the
selection box for "Errors", "Warnings", etc., to display the message in more
detail.
In conjunction with the XCI 600 controller, the message after the first
compiler run is always a warning that says "No I/O configuration is
specified". Only after the I/Os have been configured with EtherCAT®, does
this warning disappear after the next compiler run.
If errors are displayed, you can branch directly to the line of the PLC
program that caused the error by double-clicking in the error line.
Next, send the project to the controller via the Ethernet connection
(see: Figure 25).
If no connection to the controller is established, check the settings
(see: section 4.3).
Figure 25:
Transferring project to
the controller
(1) Click the <Project control dialog> button. Click the <Send> button in the
subsequent Resource control dialog.
(2) Under the Project heading, select Send again to overwrite the existing
project in the XCI.
(3) Use the <Cold> (cold start) button in the Resource control dialog to start
the program on the XCI.