Commissioning
26
Operating Manual ProNumeric XCI 600 Version 07/16
Use the PING command to subsequently perform a test to see whether the
communication connection is working (the XCI 600 controller must be
connected and started):
ping 192.168.212.2
<Enter>
Display for correct connection:
Response from 192.168.212.2: Bytes=32 Time<1ms TTL=63
Response from 192.168.212.2: Bytes=32 Time<1ms TTL=63
Response from 192.168.212.2: Bytes=32 Time<1ms TTL=63
Response from 192.168.212.2: Bytes=32 Time=1ms TTL=63
Ping statistics for 192.168.212.2:
Packages: Sent = 4, Received = 4, Lost = 0
(0% Loss),
Approx. time in milliseconds:
Minimum = 0ms, Maximum = 1ms, Mean = 0ms
You can now start MULTIPROG on the external PC. Select <
New Project>
<XCI600>
(or open an already existing project. For a more detailed
description of the procedure, see section(5).
In the PLC project, right-click on the entry <
Resource: XCI600>
and select
<
Settings>
in the context menu
(see: Figure 12).
Figure 12:
Calling the resource
settings in
MULTIPROG