7
- 147
7
Mini ECO-i System
Remote Control Functions
9. LonWorks Interface Product Manual
(SHA-LN16UG(B))
[nv11] Alarm notification
network output SNVT_switch nvoAlarm_00;
network output SNVT_switch nvoAlarm_01;
network output SNVT_switch nvoAlarm_02;
network output SNVT_switch nvoAlarm_03;
These output network variables are output when an alarm occurs at
an indoor unit, and when the alarm is reset at an indoor unit.
They are output when the LonWorks Interface or A/C unit power is
reset.
Contents
state 0: Normal
value 0 at all times
1: Alarm
[nv12] Indoor unit number with active alarm notification
network output SNVT_switch nvoAlarmIn_00;
network output SNVT_switch nvoAlarmIn_01;
network output SNVT_switch nvoAlarmIn_02;
network output SNVT_switch nvoAlarmIn_03;
These output network variables are output when an alarm occurs at
an indoor unit.
They are output when the LonWorks Interface or A/C unit power is
reset.
Contents
state 0 at all times
value Indoor unit number with
active alarm
u
2
* Value = 0 when no alarms are active.
[nv13] Room temperature notification
network output SNVT_temp_p nvoSpaceTemp_00;
network output SNVT_temp_p nvoSpaceTemp_01;
network output SNVT_temp_p nvoSpaceTemp_02;
network output SNVT_temp_p nvoSpaceTemp_03;
These output network variables are output when the indoor unit
room temperature changes.
They are output when the LonWorks Interface or A/C unit power is
reset.
When indoor units are under group control, the room temperature
of the main unit in the group is output.
Contents
Valid range
Output range:
-35.0 - 92.5
G
C
Temp. units:
0.5
G
C
* Be aware that the output temperature range may vary according to
the models of the outdoor and indoor units.
*When indoor units are under group control, the status is output from
the main unit.
[nv14] A/C unit status notification
network output SNVT_count nvoInState_00;
network output SNVT_count nvoInState_01;
network output SNVT_count nvoInState_02;
network output SNVT_count nvoInState_03;
These output network variables are output when the A/C unit status
changes.
They are output when the LonWorks Interface or A/C unit power is
reset.
[nv15] Emergency stop
network output SNVT_switch nviAllInOff;
This input network variable is used to stop the indoor units in an
emergency.
Remote-controller prohibit (start/stop prohibit) is enabled for the
stopped indoor units.
The remote-controller prohibit (temperature setting, operating
mode) status remains the same as before the units were stopped.
When emergency stop is canceled, remote-controller prohibit
(start/stop prohibit) status returns to the status prior to emergency
stop; however, the unit itself remains stopped.
If this function is not used, then it is not necessary to use this
network variable.
Contents
state 0: Cancel
value (Not used)
1: Emergency stop
[nc49] Transmission interval setting
network input config SNVT_time_sec nciSndHrtBt;
This network configuration sets the interval for automatic data
output. When the set time has elapsed, data is output automatically.
The network variables that are affected by this configuration are
the following:
nvoOnOff_0? nvoSetpoint_0? nvoHeatCool_0?
nvoOption1_0? nvoOption2_0? nvoAlarm_0?
nvoAlarmIn_0? nvoSpaceTemp_0? nvoInState_0?
Contents
The valid range is 0.0 seconds to 6553.5 seconds. If 0.0 seconds
is set, automatic data update is disabled.
The transmission interval setting is the same for all network
variables.
When the set time has elapsed, above all network variables are
output.
[nc52] Setting of minimum time secured for transmission
network input config SNVT_time_sec nciMinOutTm;
This network configuration determines the minimum interval that is
secured for output network variables.
The network variables that are affected by this configuration are the
following:
nvoOnOff_0? nvoSetpoint_0? nvoHeatCool_0?
nvoOption1_0? nvoOption2_0? nvoAlarm_0?
nvoAlarmIn_0? nvoSpaceTemp_0? nvoInState_0?
Contents
The valid range is 0.0 seconds to 6553.5 seconds.
The minimum time secured for transmission is independent for
each network variable. It is not valid between different network
variables.
Normal communications in progress (no alarms)
According to alarm code table
0
1~255
300
Indoor unit not connected (initial
communication in progress)
06-408 Mini_ECOi_SM7 11/10/06 7:24 PM Page 147
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...