3
3
- 3
Mini ECO-i System
Monitor Functions
2. Calling the Failure History
<Description>
Calls the details of past failures.
<Procedure>
Refer to the remote controller display shown in Fig. 2.
Press and hold the
(SET) and
(TEST/CHK) buttons simultaneously for 4 sec-
onds or longer to engage service check mode.
The service check display illuminates. Initially,
item code
, and the details of the most recent
alarm, are displayed. The number of the indoor
unit where the alarm occurred, and the details of
the alarm, are displayed.
To monitor a different failure history, press the
temperature setting
/
buttons to
change the failure history number (item code).
Item code
(most recent)
→
Item code
(oldest)
4 items are stored in the failure history.
Press the
(CANCEL) button to clear all items
from the indoor unit alarm history.
Press the
(TEST/CHK) button to return to
normal display.
4
3
NOTE
2
1
2
3
1
4
Fig. 2
Procedure:
Returns to normal display.
1
2
3
4
Press only when you wish to clear all history items.
( )
History clear
06-408 Mini_ECOi_SM3 11/10/06 5:19 PM Page 3
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...