7
- 99
Mini ECO-i System
Remote Control Functions
7
6. Intelligent Controller
(SHA-KT256BG)
9 Printing
9.3 Restrictions
(1)
The Intelligent Controller is adaptab
le to pr
inters of the
“PCL
” standards
, among which we ha
v
e
made sure that the following two are fully adaptable:
Laser
printer
1710 from Dell Inc.
Ink
jet
printer
Officejet Pro K550 from He
wlett-P
ac
kard Co
.
(2) Some printers need to have the Intelligent Controller powered on prior to connecting the printer
cab
le or re-po
w
er the pr
inter
.
(3) Pr
inters can be connected only to the USB por
t.
(4) Only A4-siz
e paper in v
e
rtical position can be pr
inted.
(5) Printing is available only in monochrome. Color printing is unavailable.
(6) Printing provides hardcopies (just as displayed in the screen).
(7) Refer to the operation manual for the printer for the printer-side settings, displays, and measures
to counter failures.
(8)
The f
ollo
wing alar
m dialogue will be sho
wn when pressing Pr
int in the e
v
ents of:
-
The pr
inter is not connected to the system.
-
The pr
inter is not po
w
ered on.
-
The pr
inter is off-line
.
10 Calculating air conditioner distrib
ution
The Intelligent Controller calculates energy (electricity and gas) distribution ratios utilizing the
accumulated working time (T/S ON/OFF) or the capacity value of the indoor unit.
* T/S:
Ther
mostat
10.1 Calculating simple distr
ib
ution
P
a
rameters as listed belo
w are used to calculate simple distr
ib
ution:
q
RHHi
: accumulated operation time for indoor unit i (High fan speed)
w
RHi
: accumulated operation time for indoor unit i (Medium fan speed)
e
RLi
: accumulated operation time for indoor unit i (Low fan speed)
r
SHHi
:T/S ON accum
ulated time f
or indoor unit i (High f
an speed)
t
SHi
:T/S ON accum
ulated time f
or indoor unit i (Medium f
an speed)
y
SLi
:T/S ON accumulated time f
or indoor unit i (Lo
w f
an speed)
u
Pi
: Capacity of indoor unit i (in kW)
i
k
:
W
eighing f
actor f
or po
w
er consumptions as
T/S ON and OFF
o
aHH
:
W
eighing f
actor f
or High f
an speed
a
aH
:W
eighing f
actor f
or Medium f
an speed
s
aL
: W
eighing
factor
for
Lo
w
fan
speed
* Accum
ulated oper
ation time =
T/S ON accum
ulated time +
T/S OFF accum
ulated time
Index of indoor unit i power/gas consumptions is calculated.
Here
,
“TEi”
and
TGi”
denotes the po
w
er and gas consumption inde
xes of the indoor unit i,
respectiv
ely
.
When “Object of power distribution calculation” is “T/S ON + OFF time”:
The power consumption index is calculated using “Accumulated operation time” and “T/S ON
accumulated time”; the gas consumption index using “T/S ON accumulated time”
•
For GHP:
TEi = (RHHi x aHH + RHi x aH + RLi x aL) x Pi
Formula
1
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
Formula
2
•
F
or
P
A
C:
TEi = { (RHHi x aHH + RHi x aH + RLi x aL) /K +
(SHHi x aHH + SHi x aH + SLi x aL)} x Pi
Formula
3
TGi = 0
When “Object of power distribution calculation” is “T/S ON time”:
Both the power and gas consumption indexes are calculated using “T/S ON accumulated time”.
•
For GHP:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
•
F
or
P
A
C:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = 0
•
W
eighing b
y wind speed is not carr
ied out f
or models with their speed set only as High or only as High and lo
w
.
•
Distribution ratios are not calculated when you have chosen not to perform distribution ratio calculations. (See “6.3.2 Setting
the
date, cut-off date, and distribution ratio calculation method”)
06-408 Mini_ECOi_SM7 11/10/06 7:24 PM Page 99
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...