1
-
8
Mini ECO-i System
Address Settings
1
Automatic Address Setting in Cooling Mode
G
Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.
Automatic Address Setting from Outdoor Unit
1. Perform steps 1 – 2 in the same way as for
.
3. Turn the indoor and outdoor unit power ON at all systems.
↓
4. To perform automatic address setting in
, on the outdoor unit control PCB in the refrigerant system where
you wish to set the addresses, short-circuit the mode change 2P pin (CN50). At the same time, short-circuit the automatic
address pin (CN51) for 1 second or longer, then release it. (Be sure to perform this process for one system at a time.
Automatic address settings cannot be performed for more than one system at the same time.)
↓
(Communication for automatic address setting begins,
the com
p
ressors turn ON, and automatic address setting in
Cooling mode
b
egins.
)
(All indoor units operate.)
↓
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit control PCB turn
OFF.)
5. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or longer,
then release it.
↓
(Repeat the same steps to complete automatic address setting for all units.)
↓
6. Operation from the remote controllers is now possible.
* Automatic address setting in Cooling mode cannot be done from the remote controller.
Automatic Address Setting* from the Wired Remote Controller
Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1”
1. Press the remote controller timer time
button and
button at the
same time. (Press and hold for 4 seconds or longer.)
2. Next, press either the temperature setting
or
button.
(Check that the item code is “A1.”)
3. Use either the
or
button to set the system No. to perform
automatic address setting.
4. Then press the
button.
(Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the system
returns to normal stopped status.) <Approximately 4 – 5 minutes is required.>
(During automatic address setting, “SETTING” is displayed on the remote con-
troller. This message disappears when automatic address setting is completed.)
5. Repeat the same steps to perform automatic address setting for each successive system.
Cooling mode
Case 2
Case 3B
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then release it.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
3
. Auto Address Setting
06-408 Mini_ECOi_SM1 11/10/06 5:48 PM Page 8
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...