5
- 4
Mini ECO-i System
PCB and Functions
5
Indoor Unit Control PCB Switches and Functions
Indoor unit control PCB
T10:
6P plug (yellow):
Used for remote control. (Refer to the remote control section.)
(CN061, 015) Control items:
(1)
S
tart/stop input
(2) Remote controller prohibit input
(
3
)
S
tart signal output
(4) Alarm signal output
Examples of wiring
(1) Relay junction PCB (ACC-DC24A)
(2) Power OFF reminder
EXCT:
2P plug (red):
Can be used for demand control. When input is present, forces unit to operate with
(CN07
3
, 009) the thermostat OFF.
DISP:
2P plug (white):
S
hort-circuiting this plug allows the unit to be operated by the remote controller,
(CN072
,
06
3
,
even if it is not connected to an outdoor unit.
010)
(In this case, alarm "E04," which indicates trouble in the serial communication between the indoor
and outdoor unit, does not occur.)
CHK:
2P plug (white):
Test pin.
S
hort-circuiting this pin allows the indoor FM (H fan speed), drain pump,
(CN071, 011) flap motor (F1 position), and electronic expansion valve full-open position to be checked.
However this function turns OFF if the indoor unit protection mechanism is activated. The unit can be
operated even if the remote controller and outdoor unit are not connected. However even if the
remote controller is connected, it cannot be used to operate the unit. This function can be used for
short-term tests.
JP001:
Jumper wire:
Allows selection of the T10 terminal start/stop signal. (Refer to the remote control section.)
S
tatus at shipment: Pulse signal
Jumper wire cut:
S
tatic signal (continuous signal)
FANDRIVE 2P plug (white):
This terminal sends a signal to the ventilation fan when the FAN button on the wired
(CN0
3
2, 017) remote controller is used to operate a commercially-available ventilation fan. (Refer to the remote
control section.)
Use a ventilation fan which can accept no-voltage A contact as the external input signal.
FILTER:
2P (white):
This terminal is used to connect contact input from the differential pressure switch which
(CN070, 012) detects filter clogging. When the contacts turn ON, “FILTER” is displayed on the wired remote controller.
Power LED: LED (red):
Illuminates when power is supplied. Blinks when there is a failure in the EEPROM (IC010,
002: nonvolatile memory).
EEPROM:
Nonvolatile memory:
Memory which stores the unit type data and other information. When the PCB
(IC010, 002) is replaced, remove the EEPROM from the old PCB and install it on the new PCB. If an IC failure
occurs, replace with the new IC which was provided with the service PCB, and set the necessary
information from the wired remote controller. (For the procedure, refer to the servicing technical materials.)
GRL:
For AC fan motor (CR-UXRP71B-B:
3
P (yellow))
(CN020)
For DC fan motor (CR-
S
XRP56B-B: 5P (blue))
The indoor unit power terminal plate may be a 7P,
8
P or 5P type. (Refer to the figure at below.) The basic wiring
diagram shows the 7P-type terminal plate. Therefore the terminal plate may differ from the illustrations.
Power
supply
Control
line
Remote
control line
7P-type terminal plate
8
P-type terminal plate
5P-type terminal plate
U1
R1 R2
U2
L
N
Power
supply
Remote
control line
U1
U2
L
N
Power
supply
Control
line
Remote
control line
U1
R1 R2
U2
L
N
1. Indoor Unit Control PCB
06-408 Mini_ECOi_SM5 11/10/06 5:20 PM Page 4
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...