7
- 95
Mini ECO-i System
Remote Control Functions
7
6. Intelligent Controller
(SHA-KT256BG)
6 Using the System
6.9 System Configuration Changes
An alarm message like the following appears when a system configuration change (or the
possibility of a configuration change) is detected.
If the system continues to operate after its configuration has changed, distribution ratios and other
data will be totally inaccurate. For this reason, cut-off processing must be done with the system in
the state bef
ore the change
.The f
ollo
wing message is displa
y
ed to ask y
ou to confir
m the
processing.
Operation procedure for each case is as follows.
6.9.1
When a system configur
ation change detected
This alarm message is displayed in cases such as the following.
q
“Check system Configuration” was made after removing
the outdoor and indoor units.
w
“Chec
k system Configuration”
w
as made after star
ting the
unit and found that it was different from the previous one in
configuration.
*
“Configuration” includes not only the number of units and
address b
ut also indoor unit capacity
, main/sub unit setting,
and presence/absence of an electr
ic heater
.
Here you can see the link system where the configuration has
been changed.
While this message is visible, no other operations can be performed except OK and Cancel .
T
ouch OK to perf
or
m cut-off processing with the system in the state bef
ore the change
.
T
ouch Cancel if y
ou do not need to perf
or
m cut-off processing.
T
ouch OK to chec
k the ne
w configur
ation.
If you select OK here, the current system configuration is
re-checked and the results are confirmed.
If you do not need to do this, select Cancel .
If the system has changed because of a mistake, return the system to its former state and then
touch Cancel .
Y
ou should also touch Cancel
here if y
ou mistak
enly selected Cancel
in the
pre
vious message
, e
v
en though the system cut-off processing should ha
v
e been done
.
This
returns you to the first alarm message, where you can perform cut-off processing.
While this message is visible, no other operations can be performed except OK and Cancel .
6 Using the System
While this message is visib
le
, no other operations can be perf
or
med e
xcept Do later
. or
Do no
w
. .
When touching Do later
. , this windo
w closes and other screen oper
ations are made possib
le
.
Ho
w
e
v
e
r, after a while the message will be displa
y
ed again.
T
ouch Do no
w
. to confir
m whether the configur
ation has been actually changed.
When a configur
ation change w
as detected as a result of configur
ation confir
mation, cut-off
processing is automatically perf
or
med and the post-v
ar
iation configur
ation is estab
lished.
When
there is no change in configuration, the screen e
xits configuration confir
mation processing.
F
or e
xample
, impr
udently pressing Do no
w
. while a comm
unication error message is displa
y
e
d
will result in an automatic cut-off processing to estab
lish the current configuration.
Theref
ore
,
take full care to avoid such a mistake.
When estab
lishing a configuration without making cut-off processing, press Do later
. to once
close the screen and perform “Check system Configuration” using the 6-9 screen.
After this
, proceed
“P
erf
or
m cut-off processing?”
¡
“Cancel”
¡
“Confir
m the current system
configur
ation?”
¡
“OK”
in accordance with
“6.9.1.
When a system configur
ation change detected”.
When no operation has been made on this screen f
or twelv
e hours or more
, cut-off and post-
v
a
riation configur
ation fixing processing are automatically carr
ied out.
Caution
Impr
udent cut-off processing and configuration fixing or neglecting them when necessar
y ma
y
cause a significant incon
v
enience in control.
When this alar
m message is displa
y
ed, do not operate the system and contact the store where
y
ou purchased it or its ser
vice agency
.
This message ma
y be displa
y
ed also in inspecting the air conditioner
. In such a case inf
or
m the
person in charge of ser
vice of the f
act.
6.9.2
When system configur
ation ma
y change
This alarm message is displayed in cases such as the
follo
wing.
q
The f
ollo
wing
“Detailed settings”
w
ere made from a local
remote controller
.
(f
or address
, e
xtension settings
, indoor unit capacity
, or
presence/abesnce of an electric heater)
w
Only confir
mation of
“Detailed setting”
w
as made from a
local remote controller
.
e
A
utomatic address setting w
as carr
ied out f
or an indoor
or outdoor unit.
r
An additional indoor or outdoor unit w
as installed.
*
“Configur
ation”
includes not only the n
umber of units and
address b
ut also indoor unit capacity
, main/sub unit setting,
and presence/absence of an electr
ic heater
.
06-408 Mini_ECOi_SM7 11/10/06 7:24 PM Page 95
获取更多资料
微信搜索蓝领星球
Содержание 85402843
Страница 28: ...3 MEMO 06 408 Mini_ECOi_SM3 11 10 06 5 19 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 32: ...4 MEMO 06 408 Mini_ECOi_SM4 11 10 06 5 56 PM Page 4 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 200: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 205: ...获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...
Страница 252: ...200611M DC 获 取 更 多 资 料 微 信 搜 索 蓝 领 星 球 ...