Option Communication Loss Action
Configure how the actuator will respond to a loss of option communication. The available actions are:
Off: The communication loss action is turned off.
Open Action: The actuator will run to the open limit.
Close Action: The actuator will run to the closed limit.
Stop Action: The actuator will stop.
Go To Position Action: The actuator will run to a predetermined position.
Option Communication Loss Time
The user can specify the amount of time before a loss of communications is recognised as an alarm. This
is configurable between 0 and 65.
Coms Loss Timeout Scale
The units for Option Communication Loss Time can be adjusted from Milliseconds to Seconds to suit the
specific application.
Option Communications Loss Position (%)
Upon loss of communication to the option card, the actuator will move to this position. This is only
applicable if the actuator is configured to Go To Position on loss of communications. Position is shown
as a percentage of total travel.
6.10 Control Settings
6.10.1 Set Limits
Set Open Limit
This sets the open limit at the current position of the actuator.
Set Closed Limit
This sets the closed limit at the current position of the actuator.