5.5 UPS Configuration and Status
5.5.1 UPS Configuration
Action on Loss of Power
The actuator can be configured to perform four different actions on loss of power. These are:
Closed Limit: The actuator will move to the closed limit.
Open Limit: The actuator will move to the open limit.
Stayput: The actuator will remain at the current position (Default Setting).
Go To Position: The actuator will move to a pre-determined position.
Position CVA travels to on Loss of Power (%)
The position the actuator will travel to on Loss of power, provided the Power Loss Action is set for Go To
Position. The position is a percentage of the full stroke and can be configured in increments of 0.1%.
Powerloss Action Delay timeout (sec)
The delay in seconds before the Power Loss Action is executed. The maximum allowable delay to
guarantee a failsafe action will perform is 10 seconds.
Speed of Operation during UPS action rated (%)
The speed of operation during the UPS action can be adjusted as a percentage of normal operating
speed.