6.6 Digital Input Settings
The following settings are applicable to Digital Inputs 7-14.
6.6.1 DI Function
This is where the function of a digital input can be viewed and set. The available options are:
Disabled: The selected digital input is disabled.
Remote Open: The digital input will trigger a remote open signal.
Remote Close: The digital input will trigger a remote close signal.
Remote Maintain: The digital input will trigger a remote maintain signal.
Remote ESD: The digital input will trigger a remote ESD signal.
Open Interlock: The digital input will trigger an open interlock signal (local and remote).
Close Interlock: The digital input will trigger a close interlock signal (local and remote).
Network Disable: The digital input will disable network control.
Partial Stroke: The digital input will trigger a partial stroke test.
Hand / Auto: The digital input will switch between hand and auto mode (H/W control and Analogue
control)
Velan Reset: The digital input will perform a Velan reset.
Conditional Open: The digital input will trigger an open interlock signal (remote only)
Conditional Close: The digital input will trigger an Close interlock signal (remote only)
Local / Remote Switch: The digital input will toggle between Local/ Remote producing the relevant
signals.
6.6.2 DI Input Type
Here the digital input can be configured to Normally Open or Normally Closed contact type.