50
6.7 Partial Stroke Settings
6.7.1 Partial Stroke Enable
This specifies whether partial stroke is enabled or disabled.
6.7.2 Partial Stroke Initial Position
The position that the actuator must be in before it will perform a partial stroke test. This can be set to
either the open or closed limit.
6.7.3 Partial Stroke Position (%)
The position the actuator will run to during the partial stroke test.
6.7.4 Partial Stroke Time to Position (sec)
The maximum allowable time the actuator can take to run from the initial position to the partial stroke
position. If the actuator fails to perform this part of the partial stroke test in the specified time an alarm
will trigger for partial stroke test failure.
6.7.5 Partial Stroke Time to Limit (sec)
The maximum allowable time the actuator can take to run from the partial stroke position back to its
initial position. If the actuator fails to perform this part of the partial stroke test in the specified time
and alarm will trigger for partial stroke test failure.