6.3.3 Remote Configuration
Two Wire Priority
This sets the action the actuator will take when a close and open signal are applied simultaneously.
Open Priority: The actuator will run open if both signals are applied.
Stop Priority: The actuator will stay put or stop moving if both signals are applied.
Close Priority: The actuator will run closed if both signals are applied.
Interlock Mode
This sets the mode for the interlock inputs. Refer to the actuator wiring diagram for installation details.
To operate the actuator when an interlock mode is enabled, an interlock signal must be applied in the
appropriate direction whilst providing a control signal.
Disabled: The interlock inputs are disabled.
Interlocks Enabled: Interlocks are enabled for local and remote operation.
Conditional Control Enabled: Interlocks are enabled in remote control only.
Partial Stroke On Open Interlock Enabled: The open interlock will act as a remote input to initiate a
partial stroke test.
Fast Remotes (DC Only)
For indication only, this setting reduces the minimum required control signal pulse length. (Default
Setting: Disabled) Rotork Service Engineer use only.
Push to run past limit
This function will cause the actuator control signal to be Maintained once the actuator limit setting has
been passed. (Default: Enabled)
6.3.4 Local Configuration
Local Push to Run
When enabled this changes the local open/close control knob function to a push to run operation. The
knob position must be manually maintained for the actuator to run, upon removal of the signal the
actuator will stop.
Local Close Dominant Mode
For indication only, this setting means that when a local close control command is applied it will
override all other types of control. (Default: Disabled) Rotork Service Engineer use only.
Setting Tool Local Control
This setting enables the actuator to be controlled using the open, close and stop commands on the
setting tool.
Vandal Resist Mode
The vandal resist mode is aimed at preventing unauthorised actuator operation. There are four options
available.
Vandal Resist Off: All control knobs are active and the actuator will respond to all inputs, providing the
unit is in the correct control mode. (Default)
Vandal Resist Local: In this mode the local and remote controls are disabled. The actuator can only be
controlled by the open, close and stop commands on the setting tool.
Vandal Resist Remote: In this mode all local controls, including the setting tool, are disabled. The
actuator can only be controlled by remote inputs.
Vandal Resist Local/Remote Switch: Ignore this option as it is currently not a valid setting in the IQ
software.