7-62
Troubleshooting
Table 7-37. Troubleshooting ISEL Block
Mode w= ill not leave
OOS
1. Target mode not set
2. Configuration error
3. Resource block
4. Schedule
1. Set target mode to something other than OOS.
2. BLOCK_ERR will show the configuration error bit set. SELECT_TYPE must be
set to a valid value and cannot be left at 0.
3. The actual mode of the Resource block is OOS. See Resource Block
Diagnostics for corrective action.
4. Block is not scheduled and therefore cannot execute to go to Target Mode.
Schedule the block to execute.
Status of output is bad
1. Inputs
2. OP selected
3. Min good
Block Alarms will not work 1. Features
2. Notification
1. All inputs have Bad status.
2. OP_SELECT is not set to 0 (or it is linked to an input that is not 0), and it points
to an input that is Bad.
3. The number of Good inputs is less than MIN_GOOD.
1. FEATURES_SEL does not have Alerts enabled. Enable Alerts bit.
2. LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.
1. Status Options
1. STATUS_OPTS has Propagate Fault Forward bit set. This should be cleared to
cause an alarm to occur.
OPERATION WITH
EMERSON DELTAV
About AMS and DeltaV
Software
AMS and DeltaV software allows users to manage their instrumentation, and
to perform on-line configurations of their instruments.
The ability to communicate with instruments and configure instruments on-line
facilitates instrument commissioning and loop validation.
With AMS, users can also access status and diagnostic data from smart
devices and monitor their performance.
AMS leverages the I/O capabilities of the control system to gather asset
management data without interfering with the control system’s operations.
Install the Analyzer onto DeltaV
TM
NOTE
The following procedures assume that the DeltaV and the analyzer are
installed and powered.
The following steps have to be performed to install a new device onto a
DeltaV
TM
system:
• From the start menu select DeltaV > Engineering > DeltaV Explorer.
• Select/Expand “Library” (right below DeltaV_System).
• Select “Fieldbus Devices”, using right mouse button. Click on “Fieldbus
Devices”. This will bring up a list of options.
Symptom
Possible Causes
Corrective Action
Содержание OCX 8800
Страница 2: ......
Страница 4: ......
Страница 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Страница 22: ...1 10 Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 Figure 1 7 Optional Sample Tube Support ...
Страница 33: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 2 5 Figure 2 3 Adapter Plate Installation ...
Страница 70: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 6 Figure 4 4 LOI Menu Tree Sheet 3 of 4 ...
Страница 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Страница 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Страница 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Страница 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Страница 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Страница 185: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 9 9 Figure 9 6 Remote Electronics Housing Cable Connections ...
Страница 209: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 9 33 Figure 9 26 Electronics Housing Cable Connections ...
Страница 213: ......
Страница 217: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 5 Figure 10 2 Sensor Housing Components Sheet 2 of 2 ...
Страница 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Страница 225: ......
Страница 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...