Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-30
Advanced Features
The AI function block provided with Fisher-Rosemount fieldbus devices
provides added capability through the addition of the following parameters:
ALARM_TYPE
– Allows one or more of the process alarm conditions
detected by the AI function block to be used in setting its OUT_D parameter.
OUT_D
– Discrete output of the AI function block based on the detection of
process alarm condition(s). This parameter may be linked to other function
blocks that require a discrete input based on the detected alarm condition.
VAR_SCAN
– Time period in seconds over which the variability index
(VAR_INDEX) is computed.
VAR_INDEX
– Process variability index measured as the integral of average
absolute error between PV and its mean value over the previous evaluation
period. This index is calculated as a percent of OUT span and is updated at
the end of the time period defined by VAR_SCAN.
Application Information
The configuration of the AI function block and its associated output channels
depends on the specific application. A typical configuration for the AI block
involves the following parameters:
Channel
If the device supports more than one measurement, verify that the selected
channel contains the appropriate measurement or derived value.
L_TYPE
Select
Direct
when the measurement is already in the engineering units that
you want for the block output.
Select
Indirect
when you want to convert the measured variable into another,
for example, pressure into level or flow into energy.
Select
Indirect Square Root
when the block I/O parameter value represents
a flow measurement made using differential pressure, and when square root
extraction is not performed by the transducer.
Scaling
XD_SCALE
provides the range and units of the measurement and
OUT_SCALE
provides the range and engineering units of the output.
Application Examples
Temperature Transmitter
Situation
A temperature transmitter with a range of
–200 to 450°C.
Solution
Table 7-21 lists the appropriate configuration settings, and Figure 7-8
illustrates the correct function block configuration.
Table 7-21. Analog Input
Function Block Configuration for
a Typical Temperature
Transmitter
L_TYPE
Direct
XD_SCALE
Not Used
OUT_SCALE
Not Used
Parameter
Configured Values
Содержание OCX 8800
Страница 2: ......
Страница 4: ......
Страница 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Страница 22: ...1 10 Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 Figure 1 7 Optional Sample Tube Support ...
Страница 33: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 2 5 Figure 2 3 Adapter Plate Installation ...
Страница 70: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 6 Figure 4 4 LOI Menu Tree Sheet 3 of 4 ...
Страница 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Страница 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Страница 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Страница 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Страница 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Страница 185: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 9 9 Figure 9 6 Remote Electronics Housing Cable Connections ...
Страница 209: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 9 33 Figure 9 26 Electronics Housing Cable Connections ...
Страница 213: ......
Страница 217: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 5 Figure 10 2 Sensor Housing Components Sheet 2 of 2 ...
Страница 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Страница 225: ......
Страница 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...