Standard wiring of interface
Program selection by external PLC – Menu address is binary coded
Note!
For external program selection the unit must be in ”
Automatic - Ready
” or ”
Automatic - Program invalid
” condition. On
selecting a measuring program without previous programming, the program will not be enabled and the input data IN2 to
IN6 will not be mirrored at the outputs OUT2 to OUT6. A message regarding the missing parameters will be shown.
Parallel Data Inputs
IN0
/ Measuring Start
IN1
/ Program selection
IN2
/ Binary value 1
IN3
/ Binary value 2
IN4
/ Binary value 4
IN5
/ Binary value 8
IN6
/ Binary value 16
IN7
Parallel Data Outputs
1)
OUT0
/
Meas. Start active
OUT1
/ Programm. active
OUT2
/ Binary value 1/
Ready for measuring
OUT3
/ Binary value 2
OUT4
/ Binary value 4
OUT5
/ Binary value 8
OUT6
/ Binary value 16
OUT7
/ Motor
IN0 and IN1 are flank triggered interrupt inputs. In the standard configuration the positive flank is active. Both inputs must
not be activated simultaneously. The min. time between 2 commands must be >20 ms IN1 is the strobe input for the data
inputs IN2 to IN6.
t1: < 20 ms
t2: < 4 s for filter type ”
cross correlation
“, else < 200 ms
t3: < 5 ms
1)
The output signals OUT2 to OUT6 have two different functions.
On externally activating the command ”
Program selection IN1
“ the input data IN2 to IN6 are mirrored at the outputs OUT2 to
OUT6, in order to enable transmission monitoring.
On externally activating the command ”
Measuring Start IN0
“ the measuring result and status messages will be reported. In
the standard configuration High Level = active.
t1
t3
t2
1)
0ms
1)
1)
1)
1)