As connection plug standardized shielded SUB D 9 Profibus connectors are suitable.
The use of connection plugs with integrated (switchable) terminating resistors is recommended.
If the SND40 is placed at the bus end / begin, the terminating resistor must be switched on.
View of module with connected cable
Allocation of the Profibus plug
Color of wire
D- SUB
Name
red
Pin 3
P (B-Line)
green
Pin 8
N (A-Line)
Shield
Enclosure
-
Fig. 26: Profibus module cable
Factory setting on Profibus module
1: Bus termination
downward
=
ON
upward
=
OFF
2: Slave address (00)
Both turn switches in pos. 0
(00) means, the slave address is
determined by the system configuration
Fig. 27: SND40 Profibus module