Manual
Weld Seam Detection System R4000 SND40
for Tubes, Cans and Drums
Technical records
B0059001 / Rev. 2.3
156
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
How to establish the remote connection:
1. Start ”
rhost.exe
“ on the Host-PC.
2. Start a
Telnet
session on the Host-PC (towards the SND40):
• Start the windows command shell and enter the command "cmd".
• Enter the string “
telnet 192.168.100.107
“ and confirm with <
ENTER
>.
• Enter the string “
cerdisp -c
“ and confirm with
ENTER
.
Now the SND40 display should be visible in the “
rhost
“ window, then the SND 40 software can be
remote operated via mouse.
Script for easy establishing a connection:
On the Roland website https://roland-electronic.com/en/service/software there is a script to
download, which starts the connection by double click on the unzipped file.
11.2.2.1 Allow rhost.exe in the Windows Firewall
When starting rhost.exe for the first time, this message will appear on new Windows systems:
Fig. 81: Allow program rhost.exe in the Windows Firewall
Allow the program in Home and workplace networks at this point.
11.2.2.2 Activate the Telnet Client
If the following message is displayed in the Windows command prompt, the function must be
activated in Windows (generally staring from Windows Vista):