Configuring the Option Module
3-5
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)
For example, suppose you want to use Host Parameter 17 - [DL To
Net 01] to read Parameter 2 of an optional I/O module plugged into
drive Port 4. Using the formula, the value for Host Parameter 17 - [DL
To Net 01] would be (10000 * 4) + (2) = 40002.
1. Set the value of Device Parameter 04 - [DLs To Net Cfg] to the
number of contiguous drive-to-controller Datalinks that are to be
included in the network I/O connection.
Figure 3.4
Edit DLs To Net Cfg HIM Screen
2. Reset the Option Module; see
Resetting the Option Module on
The Option Module is ready to send output data to the master
(controller). You must now configure the controller to recognize and
transmit I/O to the Option Module. Refer to
.
Selecting COS, Cyclic or
Polled (Optional)
The data exchange is the method that the Option Module uses to
exchange data on the DeviceNet network. Polled is the default and is
recommended — unless one of the other following data exchanges,
which the adapter supports, is more appropriate for your application:
If “Polled and COS” or “Polled and Cyclic” is used, the Option Module
transmits and receives the I/O from the polled messages. It transmits
only a Logic Status and Feedback in COS or Cyclic messages. Other
data is transmitted in Polled messages.
Cyclic and Polled data exchanges are configured in the scanner, so you
only need to set the I/O configuration in the Option Module. COS data
exchange must be configured in both the Option Module and the
scanner. You need to set the I/O configuration and COS parameters in
the Option Module.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit DLs To Net Cfg
0
0 << 16
•
COS (Change of State)
•
Polled and COS
•
Cyclic
•
Polled and Cyclic
•
Polled