Configuring the Option Module
3-7
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Setting a Fault Action
By default, when I/O communications are disrupted (for example, the
network cable is disconnected), the controller is idle (in program mode
or faulted) or explicit messaging for drive control is disrupted, the drive
responds by faulting. You can configure a different response to:
•
Disrupted I/O communication by using Host Parameter 33 -
[Comm Flt Action].
•
An idle controller by using Host Parameter 34 - [Idle Flt Action].
•
Disrupted explicit messaging for drive control via PCCC and the CIP
Register Object by using Host Parameter 35 - [Msg Flt Action].
Changing the Fault Action
Set the values of Host Parameters 33 - [Comm Flt Action], 34 - [Idle
Flt Action], and 35 - [Msg Flt Action] to the desired responses:
Figure 3.7
Edit Fault Action HIM Screens
Changes to these parameters take effect immediately. A reset is not
required.
!
ATTENTION: Risk of injury or equipment damage exists.
Host Parameters 33 - [Comm Flt Action], 34 - [Idle Flt
Action], and 35 - [Msg Flt Action] let you determine the
action of the Option Module and connected drive if I/O
communication is disrupted, the controller is idle, or explicit
messaging for drive control is disrupted. By default, these
parameters fault the drive. You can set these parameters so
that the drive continues to run. Precautions should be taken to
ensure that the settings of these parameters do not create a
risk of injury or equipment damage. When commissioning the
drive, verify that your system responds correctly to various
situations (for example, a disconnected network cable,
controller in idle state or explicit message control disruption).
Value Action
Description
0
Fault
The drive is faulted and stopped. (Default)
1
Stop
The drive is stopped, but not faulted.
2
Zero Data
The drive is sent 0 for output data. This does not command a stop.
3
Hold Last
The drive continues in its present state.
4
Send Flt Cfg The drive is sent the data that you set in the fault configuration
parameters (Host Parameters 37 - [Flt Cfg Logic], 38 - [Flt Cfg Ref],
and 39 - [Flt Cfg DL 01] through 54 - [Flt Cfg DL 16]).
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Comm Flt Action
Fault
0
0 << 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Idle Flt Action
Fault
0
0 << 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Msg Flt Action
Fault
0
0 << 4