3-10
Configuring the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
8. Press the MOST soft key to restore MOST Device and Host
parameters to factory defaults or press the ALL soft key to restore
ALL parameters. Or press the ESC soft key to cancel.
Important: When performing a Set Defaults, the drive may detect a
conflict and then not allow this function to occur. If this
happens, first resolve the conflict and then repeat this Set
Defaults procedure.
9. Reset the Option Module using Device Parameter 14 - [Reset
Module] or by cycling power to the drive so that the restored
parameters take effect.
Viewing the Option Module
Status Using Parameters
The following parameters provide information about the status of the
Option Module. You can view these parameters at any time.
Device Parameter
Description
03 - [DLs From Net Act]
The number of controller-to-drive Datalinks that are included in the
network I/O connection (controller outputs).
05 - [DLs To Net Act]
The number of drive-to-controller Datalinks that are included in the
network I/O connection (controller inputs).
06 - [Net Addr Src]
Displays the source from which the Option Module node address is
taken. This will be either “0” (Switches) set with the Node Address
switches shown in
or “1” (Parameters) which uses the
address from Device Parameter 07 - [Net Addr Cfg].
08 - [Net Addr Act]
The node address used by the Option Module. This will be one of
the following values:
•
The address set by the node address switches (
•
The value of Device Parameter 07 - [Net Addr Cfg].
•
An old address of the switches or parameter if they have been
changed and the Option Module has not been reset.
10 - [Net Rate Act]
The data rate used by the Option Module. This will be one of the
following values:
•
The data rate set by the data rate switch (
•
The value of Device Parameter 09 - [Net Rate Cfg].
•
An old data rate of the switch or parameter if it has been changed
and the Option Module has not been reset.