![Rockwell Automation PowerFlex 750-Series Скачать руководство пользователя страница 122](http://html.mh-extra.com/html/rockwell-automation/powerflex-750-series/powerflex-750-series_user-manual_1475453122.webp)
C-28
DeviceNet Objects
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Instance Attributes
Attribute ID Access Rule Name
Data Type
Description
6
Get
DPI Offline Read Full
STRUCT of:
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
UINT
UINT
UINT
UINT
UINT
UINT
UINT
USINT
USINT
UINT
UINT
CONTAINER
UINT
UNIT
UNIT
INT
Descriptor
Offline Minimum value
Offline Maximum value
Offline Default value
Parameter name
Offline parameter units
Online minimum parameter instance
Online maximum parameter instance
Online default parameter instance
Multiplier parameter instance
Divisor parameter instance
Base parameter instance
Offset parameter instance
Formula number
Pad byte (always zero)
Help instance
Pad word (always a value of zero)
Parameter value
Multiplier
Divisor
Base
Offset
7
Get
DPI Online Read Full
STRUCT of:
BOOL[32]
CONTAINER
(1)
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
STRING[4]
UINT
UINT
UINT
INT
USINT[3]
USINT
STRING[16]
Descriptor (see page
)
Parameter value
Minimum value
Maximum value
Default value
Next parameter
Previous parameter
Units (for example, Amps, Hz)
Multiplier
(2)
Base
Offset
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
8
Get
DPI Descriptor
BOOL[32]
Descriptor (see page
)
9
Get/Set
DPI Parameter Value
Various
Parameter value in NVS.
(3)
10
Get/Set
DPI RAM Parameter Value Various
Parameter value in temporary memory.
11
Get/Set
DPI Link
USINT[3]
Link (parameter or function block that is the source
of the value) (0 = no link)
12
Get
Help Object Instance
UINT
ID for help text for this parameter
13
Get
DPI Read Basic
STRUCT of:
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
Descriptor (see page
)
Parameter value
Minimum value
Maximum value
Default value
Parameter name
Units (for example, Amps, Hz)
14
Get
DPI Parameter Name
STRING[16]
Parameter name
15
Get
DPI Parameter Alias
STRING[16]
Customer supplied parameter name.
16
Get
Parameter Processing
Error
USINT
0 = No error
1 = Value is less than the minimum
2 = Value is greater than the maximum
18
Get
International DPI Offline
Parameter Text
Struct of:
STRINGN
STRINGN
International parameter name
International offline units