Using the I/O
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
ControlLogix Example
Creating Ladder Logic Using RSLogix 5000 (all versions)
Drive and Option Module Parameter Settings
These drive and Option Module settings were used for the example
ladder logic program in this section.
Device
Parameter
Value Description
PowerFlex 755 Drive
(Host Parameters)
01 - [DL From Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
02 - [DL From Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
03 - [DL From Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
04 - [DL From Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
05 - [DL From Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
06 - [DL From Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
07 - [DL From Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
08 - [DL From Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
09 - [DL From Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
10 - [DL From Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
11 - [DL From Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
12 - [DL From Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
13 - [DL From Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
14 - [DL From Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
15 - [DL From Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
16 - [DL From Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
17 - [DL To Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
18 - [DL To Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
19 - [DL To Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
20 - [DL To Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
21 - [DL To Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
22 - [DL To Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
23 - [DL To Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
24 - [DL To Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
25 - [DL To Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
26 - [DL To Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
27 - [DL To Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
28 - [DL To Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
29 - [DL To Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
30 - [DL To Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
31 - [DL To Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
32 - [DL To Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
20-750-DNET
Option Module
(Device Parameters)
2 - [DLs From Net Cfg] 16
Sets the number of Datalinks used to write
data from the network controller.
4 - [DLs To Net Cfg]
16
Sets the number of Datalinks used to read
data to the network controller.
TIP: The Host [DL From Net xx] parameters are inputs into the drive
that come from controller outputs (for example, data to write to a drive
parameter). The Host [DL To Net xx] parameters are outputs from the
drive that go to controller inputs (for example, data to read a drive
parameter).