Configuring the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Figure 3.3
Edit DLs From Net Cfg HIM Screen
2. Reset the Option Module; see
Resetting the Option Module on
3. Since the Logic Command and Reference is always used in the
Option Module, configure the parameters in the drive to accept the
Logic Command and Reference from the Option Module. If the
controller is going to be used for speed reference via the Option
Module, set Parameter 545 - [Speed Ref A Sel] in a PowerFlex 755
drive to the port in which the Option Module is installed (for
example, Port 4 Reference). Also, verify that the mask parameters
in the drive (for example, Parameter 324 - [Logic Mask]) are
configured to receive the desired logic from the Option Module.
Refer to the documentation for your drive for details.
The Option Module is ready to receive input data from the master
(controller). You must now configure the controller to recognize and
transmit I/O to the Option Module. Refer to
.
Enabling Datalinks To Read Data
The controller input image (drive-to-controller inputs) can have
anywhere from 0 to 16 additional 32-bit parameters (Datalinks). The
number of additional parameters is configured using Device Parameter
04 - [DLs To Net Cfg].
Important: Always use the Datalink parameters in consecutive
numerical order, starting with the first parameter. For
example, use Host Parameters 17, 18, 19, 20, and 21 to
configure 5 Datalinks to read data. Otherwise, the network
I/O connection will be larger than necessary, which
needlessly increases controller response time and memory
usage.
Host Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16]
control which parameters in the drive, Option Module, or any other
connected peripheral send the values to the network. The enhanced
PowerFlex 7-Class HIM, DriveExplorer, and DriveExecutive provide
user-friendly screens to help select the drive or peripheral by port
number and the parameter by name. As an alternate method, the
parameter value can be set manually by number using this formula:
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit DLs From Net Cfg
0
0 << 16