Configuring the Option Module
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Setting the Fault Configuration Parameters
If you set Host Parameter 33 - [Comm Flt Action], 34 - [Idle Flt
Action] or 35 - [Msg Flt Action] to “Send Flt Cfg,” the values in the
following parameters are sent to the drive after an I/O communications
fault, idle fault, and/or explicit messaging for drive control fault occurs.
You must set these parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not required.
Resetting the Option
Module
Changes to switch settings and some Option Module parameters require
you to reset the Option Module before the new settings take effect. You
can reset the Option Module by power cycling the drive or by using
Device Parameter 14 - [Reset Module].
Set Device Parameter 14 - [Reset Module] to “1” (Reset Module).
Figure 3.8
Edit Reset Module HIM Screen
When you enter “1” (Reset Module), the Option Module will be
immediately reset. An alternate method to reset the module is by power
cycling the drive. When you enter “2” (Set Defaults), the Option
Module will set ALL of its Device and Host parameters to their factory
default values. (This is the same as pressing the ALL soft key when
using the MEMORY folder method described in
Module Parameters to Factory Defaults on page 3-9
a Set Defaults, you must enter “1” (Reset Module) or power cycle the
Parameter
Description
Host Parameter 37 - [Flt Cfg Logic]
A 32-bit value sent to the drive for Logic Command.
Host Parameter 38 - [Flt Cfg Ref]
A 32-bit REAL (floating point) value sent to the drive for
Reference.
Host Parameter 39 - [Flt Cfg DL 01]
through
Host Parameter 54 - [Flt Cfg DL 16]
A 32-bit REAL (floating point) or 32-bit integer value
sent to the drive for a Datalink.
!
ATTENTION: Risk of injury or equipment damage exists. If
the Option Module is transmitting control I/O to the drive, the
drive may fault when you reset the Option Module.
Determine how your drive will respond before resetting the
Option Module.
Value Description
0
Ready (Default)
1
Reset Module
2
Set Defaults
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Reset Module
Ready
0
0 << 2
Содержание PowerFlex 750-Series
Страница 136: ...G 8 Glossary PowerFlex 750 Series Drive DeviceNet Option Module User Manual Publication 750COM UM002A EN P Notes ...
Страница 141: ...Index 5 PowerFlex 750 Series Drive DeviceNet Option Module User Manual Publication 750COM UM002A EN P Notes ...
Страница 142: ...Index 6 PowerFlex 750 Series Drive DeviceNet Option Module User Manual Publication 750COM UM002A EN P Notes ...
Страница 143: ......