Option Module Parameters
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
37 [Flt Cfg Logic]
Sets the Logic Command data that is sent to
the drive if any of the following is true:
•
Host Parameter 33 - [Comm Flt Action] is
set to “4” (Send Flt Cfg) and I/O
communications are disrupted.
•
Host Parameter 34 - [Idle Flt Action] is set
to “4” (Send Flt Cfg) and the controller is
idle.
•
Host Parameter 36 - [Msg Flt Action] is set
to “4” (Send Flt Cfg) and explicit messaging
for drive control is disrupted.
Important: The bit definitions in the Logic
Command word for PowerFlex 750-Series
drives are shown in
Default:
0000 0000 0000 0000
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
1111 1111 1111 1111
Type:
Read/Write
Reset Required: No
38 [Flt Cfg Ref]
Sets the Reference data that is sent to the
drive if any of the following is true:
•
Host Parameter 33 - [Comm Flt Action] is
set to “4” (Send Flt Cfg) and I/O
communications are disrupted.
•
Host Parameter 34 - [Idle Flt Action] is set
to “4” (Send Flt Cfg) and the controller is
idle.
•
Host Parameter 36 - [Msg Flt Action] is set
to “4” (Send Flt Cfg) and explicit messaging
for drive control is disrupted.
Default:
0
Minimum:
-3.40282 x 10
38
Maximum:
3.40282 x 10
38
Type:
Read/Write
Reset Required: No
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
[Flt Cfg DL 01]
[Flt Cfg DL 02]
[Flt Cfg DL 03]
[Flt Cfg DL 04]
[Flt Cfg DL 05]
[Flt Cfg DL 06]
[Flt Cfg DL 07]
[Flt Cfg DL 08]
[Flt Cfg DL 09]
[Flt Cfg DL 10]
[Flt Cfg DL 11]
[Flt Cfg DL 12]
[Flt Cfg DL 13]
[Flt Cfg DL 14]
[Flt Cfg DL 15]
[Flt Cfg DL 16]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
•
Host Parameter 33 - [Comm Flt Action] is
set to “4” (Send Flt Cfg) and I/O
communications are disrupted.
•
Host Parameter 34 - [Idle Flt Action] is set
to “4” (Send Flt Cfg) and the controller is
idle.
•
Host Parameter 36 - [Msg Flt Action] is set
to “4” (Send Flt Cfg) and explicit messaging
for drive control is disrupted.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required: No
Parameter
No. Name and Description