Option Module Parameters
B-5
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
33 [Comm Flt Action]
Sets the action that the Option Module and
drive will take if the Option Module detects that
I/O communications have been disrupted. This
setting is effective only if I/O that controls the
drive is transmitted through the Option
Module.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
34 [Idle Flt Action]
Sets the action that the Option Module and
drive will take if the Option Module detects that
the controller is in program mode or faulted.
This setting is effective only if I/O that controls
the drive is transmitted through the Option
Module.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
35 [Peer Flt Action]
Reserved for future use.
This parameter is functional. However, since
the Option Module does not support Peer I/O,
any entered value is not used.
36 [Msg Flt Action]
Sets the action that the Option Module and
drive will take if the Option Module detects that
explicit messaging, only when used for drive
control via PCCC and the CIP Register Object,
has been disrupted.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required: No
Parameter
No. Name and Description
Details
!
ATTENTION: Risk of injury or equipment damage exists. Host Parameter
33 - [Comm Flt Action] lets you determine the action of the Option
Module and connected drive if I/O communications are disrupted. By
default, this parameter faults the drive. You can set this parameter so that
the drive continues to run. Precautions should be taken to ensure that the
setting of this parameter does not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable).
!
ATTENTION: Risk of injury or equipment damage exists. Host Parameter
34 - [Idle Flt Action] lets you determine the action of the Option Module
and connected drive when the controller is idle. By default, this parameter
faults the drive. You can set this parameter so that the drive continues to
run. Precautions should be taken to ensure that the setting of this
parameter does not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to
various situations (for example, a controller in idle state).
!
ATTENTION: Risk of injury or equipment damage exists. Host Parameter
36 - [Msg Flt Action] lets you determine the action of the Option Module
and connected drive if explicit messaging for drive control is disrupted. By
default, this parameter faults the drive. You can set this parameter so that
the drive continues to run. Precautions should be taken to ensure that the
setting of this parameter does not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected cable).