80
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 6 Micro870 Controller Distributed Network Protocol
Unsolicited Responses For Class2
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), Unsolicited Response is disabled for Class 2
events. To prevent overflowing of the event buffer, DNP3 Master should poll for Class 2 events.
When the selection is Enabled (Checked), Unsolicited Response is enabled for Class 2 events.
Enable Unsolicited For Class3
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), Unsolicited Response is disabled for Class 3
events. To prevent overflowing of the event buffer, DNP3 Master should poll for Class 3 events.
When the selection is Enabled (Checked), Unsolicited Response is enabled for Class 3 events.
Send Initial Unsolicited Null Response On Start Up
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), the controller does not send Unsolicited NULL
Response with RESTART IIN bit on startup.
When the selection is Enabled (Checked), the controller sends Unsolicited NULL Response with
RESTART IIN bit on startup.
This selection is also used for sending the Restart IIN bit during Driver and Channel
configuration changes.
See Internal Indications on page 96
for more information.
Enable Confirmation
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), the controller sends Response packets with CON
bit set in its header under the following conditions only:
• When the response has Event data.
• When the response is multi-fragment response.
• When the Unsolicited Response is sent.
When the selection is Enabled (Checked), the controller always sends Response packets with
the CON bit set in its header, which causes the DNP3 Master to send replies confirming that it
received each Response packet without error.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...