308
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Appendix D Troubleshooting
Normal Operation
The POWER and RUN indicators are on. If a force condition is active, the FORCE indicator turns
on and remains on until all forces are removed.
Status Indicator Description
Description
State
Indicates
1
Input status
Off
Input is not energized
On
Input is energized (terminal status)
2
Power status
Off
No input power, or power error condition
Green
Power on
3
Run status
Off
Not executing the user program
Green
Executing the user program in run mode
Flashing green
Memory backup/restore in progress
4
Fault status
Off
No fault detected.
Red
Non-recoverable fault that requires a power cycle.
Flashing Red
Recoverable fault.
5
Force status
Off
No force conditions are active.
Amber
Force conditions are active.
6
Serial communications
status
Off
No traffic for RS-232/RS-485.
Green
Traffic through RS-232/RS-485.
The indicator only blinks when transmitting data. It does
not blink when receiving data.
7
Output status
Off
Output is not energized.
On
Output is energized (logic status).
8
Module status
Steady Off
No power.
Flashing Green
Standby.
Steady Green
Device operational.
Flashing Red
Minor fault
(minor and major recoverable faults).
Steady Red
Major Fault (non-recoverable fault).
Flashing Green and
Red
Self-test.
The device is performing power-on self-test (POST). During
POST, the network status indicator alternates flashing
green and red. The duration of the self-test depends on
the size of the project in the controller.
9
Network status
Steady Off
Not powered, no IP address.
The device is powered off, or is powered on but with no IP
address.
Flashing Green
No connections.
An IP address is configured, but no Ethernet application is
connected.
Steady Green
Connected.
At least one EtherNet/IP session is established.
Flashing Red
Connection timeout (not implemented).
Steady Red
Duplicate IP.
The device has detected that its IP address is being used
by another device in the network. This status is applicable
only if the device's duplicate IP address detection (ACD)
feature is enabled.
Flashing Green and
Red
Self-test.
The device is performing power-on self-test (POST). During
POST, the network status indicator alternates flashing
green and red. The duration of the self-test depends on
the size of the project in the controller.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...