Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
75
Chapter 6 Micro870 Controller Distributed Network Protocol
Max Random Delay (x1 ms)
This parameter is used with Pre-transmit Delay (x1 ms) for Collision Avoidance on RS-485
network. For more details, see
Collision Avoidance on page 112
The valid range is 0…65535. Default value is 0.
Ethernet Layer Configuration Parameters
The DNP3 over IP subsystem in the controller supports Listening End Point, TCP Dual End Point
and Datagram End Point type.
Listening End Point type supports a single TCP connection as a Server and UDP datagram.
TCP Dual End Point type supports a single TCP connection as a Server, a single TCP connection
as a Client and UDP datagram.
Datagram End Point type supports UDP datagram from DNP3 Masters. The default TCP and UDP
port numbers are 20000 and the port numbers are configurable.
The End Point type can be determined by the parameter End Point Type. According to the
parameter, the controller works as different End Point types. See
configuration.
The parameter DNP3 over IP Enable is configured in the Ethernet configuration page and other
parameters are configured in the DNP3 Slave configuration page.
Table 6 - End Point Types
End Point Type
Connection
Description
Listening End Point
A single TCP server connection
Any of the requests are accepted and the responses
are transmitted via this connection.
The unsolicited responses are transmitted via this
connection when this connection is available.
UDP datagram
Accepts only broadcast packets when DNP3
destination node is one of 0xFFFD, 0xFFFE and
0xFFFF in the request.
Dual End Point
A single TCP server connection
Any of the requests are accepted and the responses
are transmitted via this connection.
The unsolicited responses are transmitted via this
connection when this connection is available.
This connection has higher priority than the Client
connection.
A single TCP client connection
Any of the requests are accepted and the responses
are transmitted via this connection.
The unsolicited responses are transmitted via this
connection when this connection is available.
The controller does not request TCP client connection
to DNP3 Master until an unsolicited response is
generated.
UDP datagram
Accepts only broadcast packets when DNP3
destination node is one of 0xFFFD, 0xFFFE and
0xFFFF in the request.
Datagram End Point
UDP datagram only
Any of the requests are accepted and the responses
are transmitted via this connection.
All responses can be transmitted to the different
DNP3 Master port according to the configuration of
the parameters Remote UDP Port Number and Master
IP Address0. If this parameter is not set to 0, the
solicited responses are sent to the DNP3 Master port
that is configured. If this parameter is set to 0, the
solicited responses are sent to the DNP3 Master port
that sent the request.
TCP connection is not available in this configuration.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...