Chapter 6 Micro870 Controller Distributed Network Protocol
DNP3 over IP Enable
The valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), DNP3 service over Ethernet is disabled after the
configuration is downloaded to the controller.
When the selection is Enabled (Checked), DNP3 service over Ethernet is enabled after the
configuration is downloaded to the controller.
Enable Master Address Validation
The valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), the controller accepts the requests from any
DNP3 Master.
When the selection is Enabled (Checked), the controller accepts the requests only from the
DNP3 Master Node Address which is configured in the parameters
,
and
Master Node1, Master Node2, Master Node3, Master Node4 on page 73
. The maximum
number of Master Node Address for the Master Address Validation is 5.
Enable Self-Address
The valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When this bit is Disabled (Unchecked), any packets which contain the destination address
65532 (FFFCh) are ignored.
When this bit is Enabled (Checked), any packets which contain the destination address 65532
(FFFCh) are accepted and processed.
Any responses back to the DNP3 Master includes the actual configured DNP3 address of the
Micro870 controller.
Enable Access Control
The valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), the controller accepts the requests from any
DNP3 Master.
When the selection is Enabled (Checked), the controller accepts the requests only from the
DNP3 Master IP Address which is configured in the parameters Master IP Address0 to Master IP
Address4. The maximum number of Master IP Address for the Access Control is 5.
End Point Type
The valid selections are Listening, Dual and Datagram Only.
Default is Listening End Point Type.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...