0xF210
Recoverable
The expansion I/O terminator is missing.
Perform the following:
1. Power off the controller.
2. Attach the expansion I/O terminator on the last expansion I/O module on the
system.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page 313
.
0xF230
Recoverable
The maximum number of expansion I/O modules
has been exceeded.
Perform the following:
1. Power off the controller.
2. Check that the number of expansion I/O modules is not more than four.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page 313
.
0xF250
Recoverable
There is a non-recoverable error and the expansion
I/O module(s) could not be detected.
See
Corrective Actions for Recoverable Faults on page 313
0xF26z
(2)
Recoverable
An expansion I/O master fault is detected on the
system.
See
Corrective Actions for Recoverable Faults on page 313
0xF27z
(2)
Recoverable
A non-recoverable communication fault has
occurred on the expansion I/O module.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Replace the slot number z module.
0xF28z
(2)
Recoverable
Expansion I/O baudrate error.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Replace the slot number z module.
0xF29z
(2)
Recoverable
A module fault is detected on your expansion I/O
module.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Replace the slot number z module.
0xF2Az
(2)
Recoverable
Expansion I/O power failure
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Replace the slot number z module.
0xF2Bz
(2)
Recoverable
Expansion I/O configuration fault.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Correct the expansion IO module configuration in the user program to match that
of the actual hardware configuration.
• Check the expansion I/O module operation and condition.
• Replace the expansion I/O module.
0xF300
Recoverable
The memory module is present but memory module
is empty and restore operation is requested.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Check to make sure there is a valid project in the memory module.
• Download a user program and use the backup function to the memory module.
0xF301
Recoverable
The memory module’s project is not compatible
with the controller.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Check to make sure there is a user program with a controller that has the correct
controller catalog configured.
• Download a user program and use the backup function to the memory module.
0xF302
Recoverable
The password is mismatched between memory
module and controller. Only applies to Micro820
controller when Remote LCD performs the restore
operation.
This fault does not apply to Micro800 controller
firmware revision 10 and later.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Check to make sure that the user program in the memory module has the correct
password.
• Download a user program with a password and use the backup function to the
memory module.
• Use Connected Components Workbench software to enter the correct password
into the controller and perform the restore operation again.
0xF303
Recoverable
The memory module is not present and restore
operation is requested.
Check to make sure the memory module is present.
0xF0Az
(3)
Recoverable
The plug-in I/O module experienced an error during
operation.
Perform the following:
• Check the condition and operation of the plug-in I/O module.
• See
Corrective Actions for Recoverable Faults on page 313
.
0xF0Bz
(3)
Recoverable
The plug-in I/O module configuration does not
match the actual I/O configuration detected.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 313
.
• Correct the plug-in I/O module configuration in the user program to match that of
the actual hardware configuration.
• Check the condition and operation of the plug-in I/O module.
• Replace the plug-in I/O module.
Table 77 - List of Error Codes for Micro800 controllers (Continued)
Error Code
Fault Type
Description
Recommended Action
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...