78
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 6 Micro870 Controller Distributed Network Protocol
Master UDP Port Number for Initial Unsolicited
This value is used to configure Master UDP Port Number for Initial Unsolicited Response if the
parameter End Point Type is selected as Datagram Only.
The valid range is 0…65535. Default value is 20000.
Master UDP Port Number
This value is used to configure Master UDP Port Number if the parameter End Point Type is
selected as Datagram Only.
The valid range is 0…65535. Default value is 20000.
Keep Alive Interval (x 1s)
This parameter specifies a time interval for TCP Keep Alive mechanism.
If the timer times out, the controller transmits a keep-alive message. The keep-alive message
is a DNP Data Link Layer status request (FC_REQUEST_LINK_STATUS). If a response is not
received to the keep-alive message, the controller deems the TCP connection broken and
closes the TCP connection.
The valid range is 1…65535. Default value is 10.
Slave Node Address
This value is a node address of this DNP3 Slave.
The valid range is 0…65519. Default value is 1.
Local Port Number (UDP)
This value is used to configure Local UDP Port Number which is used for UDP socket listening.
The valid range is 0…65535. Default value is 20000.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...