102
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 6 Micro870 Controller Distributed Network Protocol
Data-Set Descriptors Configuration Parameters
These parameters are used to construct Data-Set Descriptors objects.
The Read and Enable Event allows assignment of characteristics to the Descriptor.
• Read – set if Data-Set is readable.
• Enable Event – set if outstation generates a Data-Set event.
Event Class – With the Enable Event checked, the event class is displayed to allow assignment
of Event Class to this Descriptor.
• 1 – Class 1
• 2 – Class 2
• 3 – Class 3
Trigger Event: Define and set this parameter to generate an event by the ladder logic to
generate timed events. Once this parameter is set by the ladder logic or communications, the
controller clears it automatically after generating an event at the end of scan.
Disable Change Event: Define and set this parameter to suppress the events generated by any
Event Occurrence Condition.
Event Occurrence Condition: The conditions of Data-Set Event for each Data-Set Descriptor
can be configured by Data-Set Event Occurrence Condition 1/2/3/4 in the DNP3 Data-Set
Descriptors Object. When one of the values that are pointing to the Event Occurrence
Condition 1/2/3/4 are changed or the criteria are met, the controller generates a Data-Set
Event, retrievable using the object Group 88, Variation 1.
The following table shows the supported conditions for Point Addressing under Event
Occurrence Conditions.
Note that a Data-set event can consume any number of event buffers, depending on the Data-
set configuration. This is only applicable for Data-set events. The event for other objects
consumes a single event buffer. When using Data-set events, increase the number of events in
the DNP3 Slave configuration.
Point Address Type
Point Type
Point Index
Event Occurrence Condition
Empty
NONE: No point type is associated. 0
No Event is generated.
Standard DNP3 Point
BI: Binary input
0…4095
When the Point Type and Point
Index are pointing a specific point,
if the value of the point is
changed, an event is generated.
B2I: Double-bit input
0…2047
CI: Counter
0…511
AI: Analog input
0…767
BCD: BCD point
0…255
Variable
Select the tag from the controller.
0
Event is generated based on the
condition of the variable tag
selected.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...