
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
243
Chapter 12 Using microSD Cards
Figure 24 - Data Log Function Block Timing Diagram
Disable(0)
Enable(1)
Disable(0)
Enable(1)
Disable(0)
Idle(0)
Busy(1)
Succeed(2)
Idle(0)
Busy(1)
Error(3)
Idle(0)
Enable(1)
Status(0)
IMPORTANT Data Log Function Block Execution
• There are three possible states for the Data Log function block: Idle,
Busy, and Complete (which includes Complete with Succeed and
Complete with Error).
• For one Data Log function block execution, the typical status starts from
Idle, then Busy and finishes with Complete. To trigger another function
block execution, the status needs to go back to Idle first.
• Idle status changes to Busy status only when Enable input signal is in
rising edge. Complete status enters Idle status when Enable input signal
is Disable status only.
• TSEnable and CfgId input parameters are only sampled at Enable input
parameter's rising edge when a new function block execution starts.
During function block execution, the input parameters of TSEnable and
CfgId are locked and any changes are ignored.
• When execution completes, the status changes from Busy to Complete. At
this stage, if input Enable is False, status changes to Idle after indicating
Complete for exactly one scan time. Otherwise function block status is
kept as Complete until input Enable changes to False.
• The data log file can only be created by the DLG instruction block. The
Connected Components Workbench software can only upload and delete
the data log file.
• There are separators in between every data variable in the data file that
is defined during configuration in the Connected Components Workbench
software.
Supported Data Types for Data Log and Recipe Function Blocks on
.
• Data variable values are sampled when data logging function block is in
Busy state. However, data logging file is only created when data logging
function block is in Complete state.
Table 59 - Supported Data Types for Data Log and Recipe Function Blocks
Data Type
Description
Example Format in Output Data Log File
BOOL
(1)
Logical Boolean with values
TRUE and FALSE
0: FALSE
1: TRUE)
SINT
Signed 8-bit integer value
-128, 127
INT
Signed 16-bit integer value
-32768, 32767
DINT
Signed 32-bit integer value
-2147483648, 2147483647
LINT
Signed 64-bit integer value
-9223372036854775808, 9223372036854775807
USINT(BYTE)
Unsigned 8-bit integer value
0, 255
UINT(WORD)
Unsigned 16-bit integer value 0, 65535
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...