Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
33
Chapter 2 About Your Controller
The following considerations determine whether the power source must be required to supply
high inrush current:
• The power-up sequence of devices in a system.
• The amount of the power source voltage sag if the inrush current cannot be supplied.
• The effect of voltage sag on other equipment in the system.
If the entire system is powered-up at the same time, a brief sag in the power source voltage
typically will not affect any equipment.
Loss of Power Source
The optional Micro800 AC power supply is designed to withstand brief power losses without
affecting the operation of the system. The time the system is operational during power loss is
called program scan hold-up time after loss of power. The duration of the power supply hold-
up time depends on power consumption of controller system, but is typically between 10
milliseconds and 3 seconds.
Input States on Power Down
The power supply hold-up time as described above is generally longer than the turn-on and
turn-off times of the inputs. Because of this, the input state change from “On” to “Off” that
occurs when power is removed may be recorded by the controller before the power supply
shuts down the system. Understanding this concept is important. The user program should be
written to take this effect into account.
Other Types of Line Conditions
Occasionally the power source to the system can be temporarily interrupted. It is also possible
that the voltage level may drop substantially below the normal line voltage range for a period
of time. Both of these conditions are considered to be a loss of power for the system.
Preventing Excessive Heat
For most applications, normal convective cooling keeps the controller within the specified
operating range. Ensure that the specified temperature range is maintained. Proper spacing
of components within an enclosure is usually sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by other equipment inside or
outside the enclosure. In this case, place blower fans inside the enclosure to assist in air
circulation and to reduce “hot spots” near the controller.
Additional cooling provisions might be necessary when high ambient temperatures are
encountered.
Master Control Relay
A hard-wired master control relay (MCR) provides a reliable means for emergency machine
shutdown. Since the master control relay allows the placement of several emergency-stop
switches in different locations, its installation is important from a safety standpoint.
Overtravel limit switches or mushroom-head push buttons are wired in series so that when
any of them opens, the master control relay is de-energized. This removes power to input and
output device circuits.
Do not bring in unfiltered outside air. Place the controller in an enclosure
to protect it from a corrosive atmosphere. Harmful contaminants or dirt
could cause improper operation or damage to components. In extreme
cases, you may need to use air conditioning to protect against heat
build-up within the enclosure.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...