214
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 10 Use the High-Speed Counter and Programmable Limit Switch
This bit can be cleared (0) by the control program and is also cleared by the HSC sub-system
whenever these conditions are detected:
• Low Preset Interrupt occurs
• Underflow Interrupt occurs
• Overflow Interrupt occurs
The Low Preset Interrupt status bit is set (1) when the HSC accumulator reaches the low preset
value and the HSC interrupt has been triggered. This bit can be used in the control program to
identify that the low preset condition caused the HSC interrupt. If the control program needs to
perform any specific control action based on the low preset, this bit would be used as
conditional logic.
This bit can be cleared (0) by the control program and is also be cleared by the HSC sub-
system whenever these conditions are detected:
• High Preset Interrupt occurs
• Underflow Interrupt occurs
• Overflow Interrupt occurs
When the HSC is in Counting mode, and PLS is enabled, this parameter indicates which PLS
element is used for the current HSC configuration.
The Error Codes detected by the HSC sub-system are displayed in this word. Errors include:
Writing to this element is not recommended except for clearing existing errors and to capture
new HSC errors.
Low Preset Interrupt (HSCSTS.LPCauseInter)
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page 204
User Program Access
HSCSTS.LPCauseInter
bit
2…9
read/write
Programmable Limit Switch Position (HSCSTS.PLSPosition)
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page 204
User Program Access
HSCSTS.PLSPosition
Word (INT)
0…9
read only
Error Code (HSCSTS.ErrorCode)
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page 204
User Program Access
HSCSTS.ErrorCode
Word (INT)
0…9
read only
Error Code Sub-element
HSC Counting Error
Code
Error Description
Bit 15…8 (high byte)
0…255
The non-zero value for high byte indicates that the HSC
error is due to PLS data setting. The value of high byte
indicates which element of PLS data triggers the error.
Bit 7…0 (low byte)
0x00
No error
0x01
Invalid HSC counting mode
0x02
Invalid High preset
0x03
Invalid overflow
0x04
Invalid underflow
0x05
No PLS data
Accumulator (HSCSTS.Accumulator)
Description
Data Format
User Program Access
HSCSTS.Accumulator
long word (32-bit INT)
read only
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...