SECTION 12: I
NTEGRATION WITH
B
UILDING
M
ANAGEMENT
S
YSTEM
(BMS)
97
5. Set the IP address on touch screen.
6. Set a unique Device Instance number. Equipment
Touch screen
The most common communication problems are the
result of not properly following the configuration
steps outlined in this manual. Review all the steps
and use the following list to check your settings.
Verify accuracy of the following:
• Proper connection wiring
• Confirm the correct BACnet network number
through the Equipment Touch
• BAS is sending requests to the proper BACnet
address of the controller
• Defined through the Touch screen display.
• To confirm settings, obtain a Modstat of the
device.
12.6 Modbus
The Modbus protocol is used mostly in the industrial
process market to communicate between PLCs (Pro-
grammable Logic Controllers).
Modbus is not a protocol that is particularly well
suited for building management because of its limited
master/slave structure. However, many companies
offer Modbus as an open protocol solution because it
is relatively easy to construct an interface.
12.6.1 To set up the Modulating Controller for
Modbus RTU or ASCII on Port 1
1. Turn off power to control board.
2. Using the rotary switches, set the controller's
address.
3. Set the Tens (10's) switch to the tens digit of the
address and set the Ones (1's) switch to the ones
digit.
4. Set the Selector DIP Switches 4 and 5 for the
appropriate communications speed (9600, 19.2k,
38.4k, or 76.8k bps).
The following example shows the DIP Switches set
for 38.4k, Port 1, and Modbus.
Содержание CORAYVAC
Страница 2: ......
Страница 4: ......
Страница 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Страница 73: ...SECTION 9 TROUBLESHOOTING 69 FIGURE 28 VFD showing a fault sign FIGURE 29 VFD input power issue ...
Страница 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Страница 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Страница 79: ...SECTION 9 TROUBLESHOOTING 75 FIGURE 34 APS does not close within 60 seconds after VFD receives run command ...
Страница 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Страница 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Страница 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Страница 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Страница 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Страница 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Страница 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Страница 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...
Страница 119: ...SECTION 14 THE ROBERTS GORDON CORAYVAC COMPLETE MODULATING HEATING CONTROL LIMITED WARRANTY 115 ...