7. MODBUS
IMS01J02-E2
146
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
AI input range number
[H-AI-A/B]
R/W C 0: 0 to 10 mV DC
1:
−
10 to
+
10 mV DC
2: 0 to 100 mV DC
3:
−
100 to
+
100 mV DC
4: 0 to 1 V DC
5:
−
1 to
+
1 V DC
6: 0 to 5 V DC
7: 1 to 5 V DC
8:
−
5 to
+
5 V DC
9: 0 to 10 V DC
10:
−
10 to
+
10 V DC
11: 0 to 20 mA DC
12: 4 to 20 mA DC
Voltage (low) input group: 0 to 8
Voltage (high) input group: 9 to 10
Current input group:
11 to 12
An input type change may only be made
within the input groups. If the input range
number is changed, all of the settings
corresponding to the channels in the
relevant module return to the default values.
The factory
set value
varies
depending
on the
specifications
when
ordering.
AI display scale high
[H-AI-A/B]
R/W
C
Span 10000 or less (Within
−
9999 to
+
10000) *
100.0
AI display scale low
[H-AI-A/B]
R/W
C
Span 10000 or less (Within
−
9999 to
+
10000) *
0.0
AI decimal point position
[H-AI-A/B]
R/W C 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
1
AI digital filter
[H-AI-A/B]
R/W
C
0.0 to 100.0 seconds (0.0: OFF)
0.0
AI moving average
[H-AI-A/B]
R/W C 0: Not provided
1: Provided
0
AI alarm 1 differential gap
[H-AI-A/B]
R/W
U
0.00 to 10.00 % of span
0.10
AI alarm 2 differential gap
[H-AI-A/B]
R/W
U
0.00 to 10.00 % of span
0.10
* The position of the decimal point differs depending on AI decimal point position (P. 146) setting.
Continued on the next page.