6. RKC COMMUNICATION
IMS01J02-E2
95
Continued from the previous page.
Name
Iden-
tifier
Digits Attri-
bute
Struc-
ture
Data range
Factory
set
value
Cascade DI function
selection
[H-CIO-A]
H3
1 R/W
M 0: Unused
1: Cascade control ON/OFF
only
2: Auto/Manual transfer only
3: DI1 valid
(Cascade control ON/OFF)
,
DI2 valid
(Auto/Manual transfer)
3
DI process selection *
[H-SIO-A]
0: Unused
1: H-SIO-A open/closed loop
control transfer only
2: Control RUN/STOP
transfer only
3: H-SIO-A open/closed loop
control transfer and
Control RUN/STOP
transfer
3
* DI process selection setting or communication setting
×
: Valid
−
: Invalid
Transfer by external
contact input
Transfer via communication
DI process selection
(Identifier H3)
H-SIO-A open/closed loop
control transfer
(Identifier SM)
Control RUN/STOP transfer
(Identifier SR)
0: Unused
×
×
1: H-SIO-A open/closed loop
control transfer only
−
×
2: Control RUN/STOP
transfer only
×
−
3: H-SIO-A open/closed loop
control transfer and
Control RUN/STOP
transfer
−
−
For Control RUN/STOP transfer (Identifier SR), see
6.2 Communication Identifier List
(P. 65)
.
Continued on the next page.