![RKC INSTRUMENT SR Mini HG SYSTEM H-PCP-J Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/rkc-instrument/sr-mini-hg-system-h-pcp-j/sr-mini-hg-system-h-pcp-j_instruction-manual_1466668074.webp)
6. RKC COMMUNICATION
IMS01J02-E2
66
Continued from the previous page.
Name
Iden-
tifier Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Heat-side manipulated
output value
[H-TIO- , H-CIO-A]
O1
6 RO C
−
5.0 to
+
105.0 %
Cool-side manipulated
output value
[H-TIO- , H-CIO-A]
O2
6 RO C
−
5.0 to
+
105.0 %
Heater break alarm status
[H-TIO-A/C/D, H-CIO-A]
AC
1
RO
C
0: OFF 1: ON
Current transformer input
measured
value 1
[H-TIO-A/C/D]
M3
6
RO
C
0.0 to 100.0 A or
0.0 to 30.0 A
Current transformer (CT)
input measured value of the
H-TIO-A/C/D module.
Current transformer input
measured
value 2
[H-CT-A]
M4
6
RO
C
0.0 to 100.0 A or
0.0 to 30.0 A
Current transformer (CT)
input measured value of the
H-CT-A module.
Set value monitor
[H-TIO- , H-CIO-A,
H-SIO-A]
MS
6 RO C
TC/RTD
input:
Within input range
Current/voltage input,
H-SIO-A:
Within display scale range
Temperature rise
completion status
[H-TIO- , H-CIO-A]
HE
1
RO
U
0: Rise not complete
1: Rise completed
Error code
[H-PCP-J]
ER
1
RO
U
0: Operations normal
1: Backup data check error
2: RAM read/write error
3: System structure error
4: Internal communications
error
5: A/D converter error
6: Adjustment data error
Continued on the next page.