7. MODBUS
IMS01J02-E2
139
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
PV bias unit selection
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0: % (of span)
1: Unit of input range
0 *
Integral time limiter at
AT end
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 1 to 3600 seconds
Setting will be valid in heat/cool control.
3600
Alarm 1 differential gap
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0.00 to 10.00
%
of span
0.10
Alarm 2 differential gap
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0.00 to 10.00
%
of span
0.10
Alarm 1 type selection
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U
Alarm 2 type selection
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U
0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 1 hold action
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U
Alarm 2 hold action
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U
0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid in deviation
alarm.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 1 interlock
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0: Not provided
1: Provided
0
Alarm 2 interlock
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0: Not provided
1: Provided
0
Alarm 1 action at input
error
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0: Normal alarm action
1: Forced alarm ON when temperature
measured value exceeds abnormal input
trigger input.
0
Alarm 2 action at input
error
[H-TIO- , H-CIO-A,
H-SIO-A]
R/W U 0: Normal alarm action
1: Forced alarm ON when temperature
measured value exceeds abnormal input
trigger input.
0
* For the ZK-1103 specification, the factory set value is 1 (Unit of input range).
Continued on the next page.